1.管道機安裝示意圖
注:具體使用請參照說明書。
2.測試標準
本儀器支持的管道鑒定標準如下表所示:
序號 標準 國家 描述
1 BS EN 12237:2003 EU Ventilation for buildings—Ductwork—Strength and leakage of circular sheet metal ducts.
2 BS EN 1507:2006 EU Ventilation for buildings—Sheet metal air ducts with rectangular section—Requirements for strength and leakage.
3 DW/143 EU HVAC—A practical guide to Ductwork leakage testing.
4 Eurovent 2/2 EU Air leakage rate in sheet metal air distribution systems.
5 SMACNA HVAC Air Duct Leakage Test manual, First edition, 1985 US Duct construction leakage classification, expected leakage rates for sealed and unsealed ductwork, duct leakage test procedures, recommendations on use of leakage testing, types of test apparatus and test setup and sample leakage analysis.
6 AABC US Associated Air Balance Council AABC Standard
7 GB50243 GB 通風與空調工程質量驗收規范
本儀器的EU標準兼容以下三種歐洲標準:
(1) EU Standards EN12237
Air Tightness Class Air Leakage Limit (fmax) m3/s/m2 Static Pressure Limit (ps) Pa
Negative Positive
A (0.027×P_t^0.65)/1000 500 500
B (0.009×P_t^0.65)/1000 750 1000
C (0.003×P_t^0.65)/1000 750 2000
D (0.001×P_t^0.65)/1000 750 2000
* Class D ductwork is only for special apparatus
(2) EU Standards EN1507
Air Tightness Class Air Leakage Limit (fmax) m3/s/m2 Static Pressure Limit (ps) Pa
Negative Positive at pressure class
1 2 3
A (0.027×P_t^0.65)/1000 200 400
B (0.009×P_t^0.65)/1000 500 400 1000 2000
C (0.003×P_t^0.65)/1000 750 400 1000 2000
D* (0.001×P_t^0.65)/1000 750 400 1000 2000
* Class D ductwork is only for special apparatus
(3) EU Standards Dw/143
Duct Pressure Class Static Pressure Limit Maximum Air Velocity m/s Air leakage limits l/s/m2
Positive Pa Negative Pa
Low-pressure – Class A 500 500 10 0.027×P_t^0.65
Medium pressure – Class B 1000 750 20 0.009×P_t^0.65
High pressure – Class C 2000 750 40 0.003×P_t^0.65
注:Pt為管道中的靜壓。
3.儀器設置
(1)單位設置,采用DW/143標準時,風量單位設置為l/s。